Abstract
This paper proposes a control approach to achieve balanced grid currents in Three-Level Voltage-Source Inverters connected to the utility under dip or unbalanced condition. Fast sequence separation method for symmetrical components is used concurrently with Linear Quadratic Regulator in the current controller, in order to take advantage of the multivariable structure of the system. The harmonic content of the grid voltages can affect the type of sequence separation method to be used. Controller parameters are tuned by simulation. Experimental results have been obtained with a distorted grid, with significant harmonic content, under dip or unbalance condition, verifying the validity of the proposed control approach.
Original language | English |
---|---|
Title of host publication | 2007 European Conference on Power Electronics and Applications, EPE |
DOIs | |
Publication status | Published - 1 Dec 2007 |
Event | 2007 European Conference on Power Electronics and Applications, EPE - Aalborg, Denmark Duration: 2 Sept 2007 → 5 Sept 2007 |
Other
Other | 2007 European Conference on Power Electronics and Applications, EPE |
---|---|
Country/Territory | Denmark |
City | Aalborg |
Period | 2/09/07 → 5/09/07 |
Keywords
- Distributed power
- Voltage Source Converter (VSC)
- Voltage Source Inverters (VSI)
- Wind energy
ASJC Scopus subject areas
- Energy Engineering and Power Technology
- Electrical and Electronic Engineering